D2 PTV1

Application-

Speed Control Feedback Application
Metering & Relay Panels for Substations

Overview-

Voltage transducer
Input AC voltage
Output (DC) single or dual
Accuracy 0.5%
Operations
The input Voltage signal is scaled down through Interposing potential transformer. The scaled down signal is fed to a precision rectifier stage, its output is processed to provide DC Voltage / Current output proportional to input AC voltage. The output signal is calibrated for RMS value.

Description

Technical Specifications

Auxiliary Supply 110 / 240 V AC, ± 20% 24 / 48 / 110 / 220 V DC ±20%

Power Consumption
Power Consumption 3.5 VA – AC, 4 VA – DC

Input Value
I in NA
V in 110 / 240 / 415 V

DC Output (Single / Dual)
DC Output (Single / Dual) 0 – 1 mA, 0 – 10 mA, 0 – 20 mA, 4 – 20 mA, 0 – 5 V, 0 – 10 V Other optional on request

No of Signal Output
No of Signal Output Single (Optional Dual Output)

Response Time
Response Time Less than 500 milliseconds

Temperature
Temperature 0°C to + 55°C

Humidity
Humidity Up to 95% Rh non condensing

Dimensions (L x W x D) (mm)
Dimensions (L x W x D) (mm) 75 x 56.5 x 117.5

Weight
Weight 440 gms

Common Specifications
Output Load Resistance (Rout)
For Current OutputMax. 10V/I out (Optional Max. 15V/Iout)
For Voltage Output 10 Kohm (min.)

Output Ripple
Output Ripple Less than 0.5% of span (peak to peak)

Auxiliary Supply Burden
Auxiliary Supply BurdenLess than 4 VA

Insulation Resistance
Insulation Resistance More than 100 Mohms at 500 V DC

Zero Span Adjustment
Zero Span Adjustment Optionally provided

Terminals
Terminals Suitable for 2.5 sq.mm wires

Enclosure Type
Enclosure Type ABS Plastic, Ingress Protection IP40