D2 VCT1

Application

  • Auto Mains Failure Panels.
  • Generator Set Panels.
  • Battery Charger Panels.
  • Inverter Panels.
  • DC Drive Control panels.
  • UPS

Overview

  • 3-Phase 3-Wire and 3-Phase 4-Wire (selectable) Under & Over voltage,
  • Microcontroller based design,
  • Auto/Manual Reset,
  • Adjustable under/over voltage settings,
  • Absolute values for UV/OV,
  • Adjustable trip delay & ON delay,
  • 2 CO output relay (or selectable 1CO for UV, 1CO for OV) Failsafe-non-failsafe selectable
Category:

Description

Technical Specification

Supply Voltage

  • System 100-120/220-240/380-440V AC -25%+20%,48-63 Hz

Output Relay Contact

  • Output Relay Contact 1 CO + 1 CO / 2 CO

Trip Setting(Volts)

  • Under Voltage    Ph Ph Setting:
    For 380-440V AC: 285-425V AC (Variable)
    For 220-240V AC: 165-225V AC (Variable)
    For 100-120V AC: 75-115V AC (Variable)
                                 Ph N Sensing:
    For 380-440V AC: 165-245V AC (Variable)
    For 220-240V AC: 95-135V AC (Variable)
    For 100-120V AC: 45-65V AC (Variable)
  • Over Voltage       Ph Ph Setting:
    For 380-440V AC: 400-520V AC (Variable)
    For 220-240V AC: 230-290V AC (Variable)
    For 100-120V AC: 105-145V AC (Variable)
                                 Ph N Sensing:
    For 380-440V AC: 230-310V AC (Variable)
    For 220-240V AC: 130-170V AC (Variable)
    For 100-120V AC: 60-80V AC (Variable)

Trip Time Delay

  • Trip Time Delay 1-10 Sec (Variable) UV/OV/NF

Power on Delay

  • Power on Delay 1-10 Sec (Variable)

Resetting Mode

  • Resetting Mode Auto / Manual Reset

Weight

  • Weight 300 gms.

Dimensions (mm)

  • Overall (L x W x D) 76 x 56.5 x 117.5
  • Mounting (L x W) 67 x 46 / 35 mm rail Mount

Note:

  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)