D5 PTW2

Application-

Control & Relay Panel
Metering Panels
Motor Testing Equipments
Transformer Panels
Cogeneration /Captive Power Plants
Paper Mills, Sugar Plant
Overview-

Reactive Factor Transducer
Input 3-phase voltage & current
Output Single or Dual (DC)
Accuracy 0.5%

Operations
The input Voltage and current signals are scaled down through interposing potential and current transformer. In case of reactive transducers the voltage signals are 900 phase shifted. The scaled down signals are fed to precision multipliers working on time division multiplication principle. The multiplier output is processed to provide DC Voltage / Current output signal proportional to input active / reactive power. For Signal Phase network, only Active Power Transducer is offered. Fro 3 Phase 3 Wire or 3 Phase 4 Wire electrical networks both Active and Reactive Power Transducers are offered for balanced as well as unbalanced load conditions.

Category:

Description

Technical Specifications

Auxiliary Supply Self Powered, 110/240 V AC, 24 / 48 / 110 / 220 V DC ± 20 %

Power Consumption
Power Consumption 3.5 VA – AC, 4 VA – DC

Input Value
I in 1 A / 5 A
V in 110 / 415 V

DC Output (Single / Dual)
DC Output (Single / Dual) 0 – 1 mA, 0 – 10 mA, 0 – 20 mA, 4 – 20 mA, 0 – 5 V, 0 – 10 V

No of Signal Output
No of Signal Output Single (Optional Dual Output)

Response Time
Response Time Less than 500 milliseconds

Input / Output isolation
Input / Output isolation Galvanic

Temperature
Temperature 0°C to + 55°C

Humidity
Humidity Up to 95% Rh non condensing

Dimensions (L x W x D) (mm)
Dimensions (L x W x D) (mm)75 x 150 x 113

Weight
Weight 1200 gms.

Common Specifications
For Current OutputMax. Max. 10V/I out (Optional Max. 15V/Iout)
For Voltage Output 10 Kohm (min.)

Output Ripple
Output Ripple Less than 0.5% of span (peak to peak)

Auxiliary Supply Burden
Auxiliary Supply Burden Less than 4 VA

Insulation Resistance
Insulation Resistance More than 100 Mohms at 500 V DC

Zero Span Adjustment
Zero Span Adjustment Optionally provided

Terminals
Terminals Suitable for 2.5 sq.mm wires

Enclosure Type
Enclosure Type ABS Plastic, Ingress Protection IP40