D5 MFT1

Application-

Suitable for Panels in Process Plants, Diesel Generator sets, Central Control Rooms etc.
C & R Panel
Material handling Systems

Overview-

This is a modified version of earlier Microwarn 9600 model which has been discontinued.

Microwarn O600 is now more compact than before with reduced depth. Also it can have 3 output relay for extra function. Microwarn 0600 consists of 3 basic sections:

The Power PackThe CPUThe Facia
Notes
COVER MOUNTING SCREWSTERMINAL STRIP FAULT INPUTLED BOARDPOWER SUPPLY CONNECTORSLOT FOR MOUNTING CLAMPTERMINAL FOR EXTERNAL PUSH BUTTONFACIAC COVERDIP SWITCHESFUSERELAY OUTPUTSMPS + CPU CARD
The Power Pack
The Microwarn 0600 is powered by a highly reliable and noise free, specially designed power supply. It converts the available power source (AC/DC voltage supply) into a regulated and filtered DC output, which is fed to the annunciator unit
The CPU
This is the Central Processing Unit of Microwarn 0600 which scans and processes the incoming fault signals from the various potential free field contacts and drives the corresponding LED windows and the audible devices in order to announce the fault, according to the operating sequence selected
The Facia
This section consists of facia windows illuminated by “Super Bright LEDs” on occurrence of any fault. The Super Bright LEDs ensure a long and absolutely maintenance free window life along with a good visibility, and have very low power consumption
NO/NC T/NT or sequence selection DIP switches are located outside, hence programming is now possible without opening the unit

Models of 12, 8, 6 windows are available. 8 and 6 window models are with built-in push buttons.

Optional Features
3rd Supervisory Relay
The Power Pack
The Microwarn 0600 is powered by a highly reliable and noise free, specially designed power supply. It converts the available power source (AC/DC voltage supply) into a regulated and filtered DC output, which is fed to the annunciator unit
The CPU
This is the Central Processing Unit of Microwarn 0600 which scans and processes the incoming fault signals from the various potential free field contacts and drives the corresponding LED windows and the audible devices in order to announce the fault, according to the operating sequence selected
The Facia
This section consists of facia windows illuminated by “Super Bright LEDs” on occurrence of any fault. The Super Bright LEDs ensure a long and absolutely maintenance free window life along with a good visibility, and have very low power consumption
NO/NC T/NT or sequence selection DIP switches are located outside, hence programming is now possible without opening the unit

Models of 12, 8, 6 windows are available. 8 and 6 window models are with built-in push buttons.

Optional Features
3rd Supervisory Relay

Category:

Description

Technical Specifications

Supply Voltage
Supply Voltage 24/30/48/ V DC,20-60 V AC/DC, 90-270V AC/DC

Windows
Windows 12/8/6

Window Sizes
Window Sizes 45 x 45 mm

Display Device
Display Device Super bright high efficiency low power consuming LED’s

Facia Type
Facia Type Front Replaceable

Window/LED Colours
Window/LED Colours Standard colour available RED, Optional colours Yellow / Amber,                                          Green

Flash Rate
Flash Rate Fast – 60 flashes/min. Slow – 30 flashes/min.

Response Time
Response Time 40 msec.

Input Signal
Input Signal Potential free contacts (NO or NC site selectable)

Grouping
Grouping site selectable (Trip / Non Trip)

Interrogation Voltage
Interrogation Voltage + 12 V DC

Output Contacts
Output Contacts 1 NO + 1 NO (optional) + 1 NO

Architecture
Architecture Integrated

Operational Sequences
Operational Sequences(site selectable) ISA Standards sequences – Auto/Manual/First-                                                                                up/Ringback (optional) OR any other sequence

                                                                    on request

Operational Temp
Operational Temp -5° C to 60°C

Power Consumption
Power Consumption 1.5 Watts per Window (Max.)

Optional
Optional AC-DC fail Annunciation

Dimensions (mm)
Panel Cutout (L x W) 153 x 203
Overall (L x W x D)166 x 216 x 82

Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) * CE marked products available on request.