MBAS 08

Application-

  • Plants, Diesel Generators
  • Control Rooms
  • C & R Panel
  • Material handling Systems
  • Instrumentation Panel
  • Transformer Panel

Overview-

Most compact alarm Annunciator with improved window design and all major features of MBAS 0600 Annunciator. Models with built-in Buzzer & Push buttons also available.

Category:

Description

Supply Voltage 90 to 270 VAC/DC 24 VDC /30 VDC /48VDC

Supply Frequency [FOR AC]50 / 60 Hz ± 3%

Windows 4 / 6 / 7 / 8 [max]

Display (Window) Window lenses replaceable Legends replaceable.

Window Dimensions
Small 37 X 17 mm
Big 37 X 27 mm. for 4 Windows model only

Power Consumptions 1.5 Watts per Window (Max)

Flash Rate 50 – 60 Flash per min. in fast flashing
                    20 – 30 Flash per min. in slow flashing

Operating Sequence S1, S2, S3 (Optional), S4 (Site Selectable)

Other Features NO / NC and Grouping (Trip/Non trip) Selection
                             Supervisory Contact output.

Optional Features Any other operating sequence
                                 RS232 / RS485 Output
                                 Man / Unmanned Feature
                                  Supply fail Annunciation 

Input Signal Potential Free contacts

Input Interrogation Voltage +12 VDC

LED Colour in Windows Red, Green, Yellow (Amber), Blue, White.

Output Contacts 1 NO + 1 NO [For Hooter]
                                1NO For Ring back or Supervisory contact (Optional)

Output Contact Rating 5 Amp, 240V AC (Resistive)

Inbuilt Push Buttons 4 NOS. (Test, Mute, Accept, Reset) Membrane type (Optional)

Communication RS232 / RS485 (MODBUS RTU/ASCII) (Optional)

Operational Temp. Limit -5°C to 60°C

Humidity Upto 95% Rh

Unit Dimensions
Overall (L x W x D)96 x 96 x 76 mm
Cutout (L x W ) 92 x 92 mm

Weight 350gm

PROGRAMMING OF MBAS 08
SR. NO. KEY OPERATION MODE OF OPERATION WINDOW STATUS WDL STATUS
1 Normal Run Mode As per operation Flashing @ 1 flash/sec.
2 TEST + ACK
Pressed (for 5 Sec.)
Sequence selection Windows
fast flashes for
2 to 3 sec.
W1 – ON – S1
W2 – ON – S2
W3 – ON – S3
W4 – ON – S4
Flashing @ 1 flash/sec.
3 TEST + ACK
Pressed (for 5 Sec.)
NO / NC selection W – ON – NO
W – OFF- NC
Off
4 TEST + ACK
Pressed (for 5 Sec.)
Grouping selection W – ON – Group 1
W – OFF- Group 2
Steady On
5 TEST + ACK
Pressed (for 5 Sec.)
Device ID selection As per chart in Manual Fast Flashing
6 Auto exit after 5 Seconds