Description
Technical Specification
Supply Voltage
- System 220 – 240 / 380 – 440 V AC ± 20%
- Auxiliary 100 – 120 / 220 – 240 / 415 V AC ± 20%, 48 – 63 Hz.
Output Contact
- Output Relay Contact 2 CO
Ext. Input
- Input Signal 1 Amp / 5 Amp CT Secondary OR 250 mA / 500 mA
Trip Setting
- Phase Sequence Yes
- Phase to Phase Unbalance 50% of Motor Current (Fixed)
- Under Current (Dry Run) 40% to 80% od set current (Adjustable with Bypass Facility)
- Over Load As per Inverse Time Characteristics
Trip Time Delay
- On Phase Failure 4 Sec ± 1 Sec
- Dry Run 4 Sec ± 1 Sec
- Over Load As per Inverse Time Characteristics 2 / 5 / 10 / 15 / 20 sec. (Selectable)
Resetting Mode
- Resetting Auto / Manual / Remote
Weight
- Weight 250 gms (Approx.)
Dimensions (mm)
- Overall (L x W x D) 76 x 56.5 x 117.5
- Mounting (L x W) 67 X 48 Center to Center / 35 mm DIN Rail
Note:
- Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)