D3 MPR1

Suitable for Panels in Following Applications:

  • Heavy Duty Motors
  • Crane Motors
  • Screw Compressors
  • AHU Fan Motors
  • HT Motors
  • Pump protection
  • Pump House Automation

Overview

  • Micro controller based.
  • Sensing current
  • Protecting against Phase Failure, Unbalance, Phase sequence, overloading, Over current/Short circuit, locked rotor.
  • Auto/Manual resetting
  • Adjustable trip settings for UC/OC, O/L, Locked rotor &earth fault.
  • Start-up delay adjustable
  • 2x1CO output relays and last ten faults logging.

Description

Technical Specification

Supply Voltage

  • System 380 – 440 V AC ± 20%, 45 – 55 Hz.
  • Auxiliary 90 – 270 V AC / DC, 415 V AC

Output Relay Contact

  • Output Relay Contact 2 CO

Trip Setting

Parameters Range Resolution Fact setting Trip delay Range Factory setting By Pass Facility Reset  type
Ext. CT 50 – 600 5 Amp 100 Amp NA NA NA NA
Set current (FLC) 20 to 100 % of FLA 1 Amp 100 Amp NA NA NA NA
Over Load Above 115 % of Set Value NA NA IDMT class 2,5,10,15,20, 30 sec 2 sec Yes Auto/ Manual
Start up delay 0 – 60 sec 1 sec 10 sec NA NA NA NA
Under Current 30 – 90% 5% 50% 1- 60 sec 5 sec Yes Auto/ Manual
Over Current 110 – 350% 5% 200% 1 -10 sec 2 sec Yes Auto/ Manual
Current Unbalance 20 – 60 % 5% 50% 4 sec Fixed 4 sec Yes Auto/ Manual
Current Single Phasing Yes NA NA 4 sec Fixed 4 sec Yes Auto/ Manual
Reverse Phase Yes NA NA Instant ( < 2 sec) NA Yes (Password protected) Auto/ Manual
Rotor Lock 200- 800% 50% 700% Instant ( < 2 sec) NA Yes Auto/ Manual
Earth Fault 10- 100% 10% 30% 0.5-10 sec 0.5 sec Yes Auto/ Manual

Fault Memory

  • Fault Memory Last 10 faults

Resetting Mode

  • Resetting Auto / Manual

Display

  • Display 8 X 2 AN LCD

Weight

  • Weight 400 gms 

Dimensions (mm)

  • Overall (L x W x D) 100 x 73 x 113
  • Mounting (L x W) 35 mm DIN Rail

Note:

  • Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)